Customization: | Available |
---|---|
Type: | Signal Type Arrester |
Structure: | Protective Gap |
Still deciding? Get samples of US$ 18.6/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
AC Surge Protector Device T3, Class D, Class III SPD
The AC Surge Protective Device SPD T3, Class D, Class III TLP product line is distinguished by its modular devices' high-performance specifications and uncomplicated AC series design. The devices integrate safety and usability into a single module. They are useful for protecting terminal equipment in industrial electronic environments due to their low voltage protection level and extensive protection against common-mode and differential-mode interference.
Product Benefits
Technical Data
IEC Electrical | |||||
Nominal AC Voltage (50/60Hz) | Uo /Un | 230V | |||
Maximum Continuous Operating Voltage (AC) | Uc | 275V | 320V | 385V | 420V |
Nominal Discharge Current (8/20 μs) | In | 5kA | 5kA | 5kA | 5kA |
Maximum Discharge Current (8/20 μs) | Imax | 10kA | 10kA | 10kA | 10kA |
Withstand on Combination waveform-Class III test | Uoc | 10kV | 10kV | 10kV | 10kV |
Voltage Protection Level | Up | 1000V | 1000V | 1200V | 1300V |
Response Time | tA | <25ns | |||
Back-Up Fuse (max) | 125A gL / gG | ||||
Short-Circuit Current Rating (AC) | I SCCR | 25kA | |||
TOV Withstand 5s | UT | 335V | |||
UT | 440V | ||||
TOV 120min | Mode | Safe Fail | |||
Number of Ports | 1 | ||||
UL Electrical | |||||
Maximum Continuous Operating Voltage (AC) | MCOV | 275V | 320V | 385V | 420V |
Voltage Protection Rating | VPR | 900V | 1000V | 1200V | 1400V |
Nominal Discharge Current (8/20 μs) | In | 5kA | 5kA | 5kA | 5kA |
Short-Circuit Current Rating (AC) | I SCCR | 25kA | 25kA | 25kA | 25kA |
Mechanical & Environmental | |||||
Operating Temperature Range | Ta | -40oF to +158oF [-40oC to +70oC] | |||
Permissible Operating Humidity | RH | 5%…95% | |||
Atmospheric pressure and altitude | 80k Pa … 106k Pa / -500m … 2000m | ||||
Terminal Screw Torque | Mmax | 39.9 Ibf·in [2.0~2.5 N.m] | |||
Conductor Cross Section (max) | 2 AWG (Solid, Stranded) / 4 AWG (Flexible) | ||||
35mm2 (Solid, Stranded) / 25mm2 (Flexible) | |||||
Mounting | 35mm DIN Rail, EN 60715 | ||||
Degree of Protection | IP20(built-in) | ||||
Housing Material | Thermoplastic: Extinguishing Degree UL 94 V-0 | ||||
Thermal Protection | Yes | ||||
Operating State / Fault Indication | Green: ok / Red: failure | ||||
Remote Contacts (RC) | Optional | ||||
RC Switching Capacity | AC:250V / 0.5A; DC:250V / 0.1A; 125V / 0.2A; 75V / 0.5A | ||||
RC Conductor Cross Section (max) | 16AWG (Solid) / 1.5mm2 (Solid) |
Product model | |||||||
IEC Electrical | |||||||
Nominal AC Voltage (50/60Hz) | Uo /Un | 230V | |||||
Maximum Continuous Operating Voltage (AC) | Uc | 275V/255V | 320V/255V | 385V/255V | 420V/255V | ||
Nominal Discharge Current (8/20 μs) | In | 5kA/5kA | 5kA/5kA | 5kA/5kA | 5kA/5kA | ||
Maximum Discharge Current (8/20 μs) | Imax | 10kA/10kA | 10kA/10kA | 10kA/10kA | 10kA/10kA | ||
Withstand on Combination waveform-Class III test | Uoc | 10kV | 10kV | 10kV | 10kV | ||
Voltage Protection Level | Up | <1000V / 1000V | <1000V / 1000V | <1200V / 1000V | <1300V / 1000V | ||
Response Time | tA | <25ns / 100ns | |||||
Back-Up Fuse (max) | 125A gL / gG | ||||||
Short-Circuit Current Rating (AC) | I SCCR | 25kA | |||||
TOV Withstand 5s | UT | 335V | |||||
UT | 440V | ||||||
TOV 120min | Mode | Safe Fail | |||||
Number of Ports | 1 | ||||||
UL Electrical | |||||||
Maximum Continuous Operating Voltage (AC) | MCOV | 275V | 320V | 385V | |||
Voltage Protection Rating | VPR | 900V | 1000V | 1200V | |||
Nominal Discharge Current (8/20 μs) | In | 5kA | 5kA | 5kA | |||
Short-Circuit Current Rating (AC) | I SCCR | 25kA | 25kA | 25kA | |||
Mechanical & Environmental | |||||||
Operating Temperature Range | Ta | -40oF to +158oF [-40oC to +70oC] | |||||
Permissible Operating Humidity | RH | 5%…95% | |||||
Atmospheric pressure and altitude | 80k Pa … 106k Pa / -500m … 2000m | ||||||
Terminal Screw Torque | Mmax | 39.9 Ibf·in [2.0~2.5 N.m] | |||||
Conductor Cross Section (max) | 2 AWG (Solid, Stranded) / 4 AWG (Flexible) | ||||||
35mm2 (Solid, Stranded) / 25mm2 (Flexible) | |||||||
Mounting | 35mm DIN Rail, EN 60715 | ||||||
Degree of Protection | IP20(built-in) | ||||||
Housing Material | Thermoplastic: Extinguishing Degree UL 94 V-0 | ||||||
Thermal Protection | Yes | ||||||
Operating State / Fault Indication | Green: ok / Red: failure | ||||||
Remote Contacts (RC) | Optional | ||||||
RC Switching Capacity | AC:250V / 0.5A; DC:250V / 0.1A; 125V / 0.2A; 75V / 0.5A | ||||||