Customization: | Available |
---|---|
Type: | Low-voltage |
Structure: | Double-column Disconnector |
Still deciding? Get samples of US$ 20/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
EDS1 Series isolator Parallel wiring, larger aperture, much easier wiring. Suitable for distribution box module with lock installation. Arc extinction time less than 3ms.Modular design. 2 poles & 4poles optional. Comply with IEC60947-3(ed.3.2):2015, DC-PV1standard.
EDS1 series isolation switch is suitable for a power system with rated voltage DC 1200V or below and rated current 32A or below. The product can be used for infrequent switching-on and switching-off and can disconnect 1 - 2 MPPT lines at the same time. It is especially suitable for isolating lines in HVDC transmission and distribution systems, such as cutting off the high voltage DC current between solar panels and inverters
Technical Data
Main Parameters | EDS1/N EDS1/S | ||
Rated Insulation Voltage | Ui | V | 1500 |
Rated thermal current | Ith | A | 32 |
Rated impulse withstand voltage | Uimp | V | 8000 |
Rated short-circuit making capacity | Icw | A | 1 kA,1 S |
Maximum cable section(incl.jumper) | |||
Solid | mm2 | 4-16 | |
Flexible | mm2 | 4-10 | |
Flexible(+multicore cable end) | mm2 | 4-10 | |
Torque | |||
Tightening torque terminal screws M4. | Nm | 1.2-1.8 | |
Tightening torque shell mounting screws ST4.2(304 stainless steel) | Nm | 1.5-2.0 | |
Tightening torque knob screws M3 | Nm | 0.5-0.7 | |
Switching on or off Torque | Nm | 0.9-1.3 | |
The wiring Torque on Base | Nm | 1.1-1.4 | |
General parameters | |||
Knob Positions | 12 o'clock,OFF 3 o'clock,ON 9 o'clock,OFF 12 o'clock,ON | ||
Electrical Life |
Actual | 3000 Cycles | |
Standard | 300 Cycles | ||
Mechanical Life |
Actual | 10000 Cycles | |
Standard | 10000 Cycles | ||
Number of DC poles | 2 or 4 | ||
Operation temperature | °C | -40 to +85 | |
Storage termperature | °C | -40 to +85 | |
Pollution degree | 3 | ||
Overvoltage category | III | ||
IP rating of shafte and mounting nul | IP66 |
Data according to AS60947-3
Main Contacts | Voltage | EDS1/N32 |
Rated thermal current Ithe | 32 A | |
Rated insulation voltage Ui | 1500 V | |
Distance of contacts(per pole) | 8 mm | |
Rated operational current Ie(DC-PV2) | ||
4 layers, only 2layers in series, with two load 1 2 |
300V | 32 A |
600V | 32 A | |
800V | 16 A | |
1000V | 9 A | |
4 layers, 4 layers in series, with one load 1 2 3 4 |
300V | 32 A |
600V | 32 A | |
800V | 32 A | |
1000V | 32 A |