Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Electric Type |
Still deciding? Get samples of US$ 9.9/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product Benefits :
When two poles are placed adjacent to each other, these channels form a tunnel resulting in effective air circulation around individual poles
Choice to use Busbar and/or cable in the same terminal,provides reliable termination
Two step snapping mechanism for easy & efficient mountion in 35mm DIN Rail steadily
Residual current-operated circuit breakers (RCBO)with overcurrent protection are mainly suitable for applications that require both overcurrent protection (overload and short circuit)and ground-fault current protection. It can detect faults and trip in time to ensure the safety of staff and equipment. Can be applied to energy management systems, power supply, and distribution network automation, residential power monitoring, and complete sets of equipment.
Technical Data
Electrical Features | |
Mode | Electronic |
Type | A / AC |
Tripping curve | B C D |
Pole No. | 2P |
Rated voltage | 240V~ |
Rated frequency | 50/60Hz |
Overload Current Protection Characteristics | ||||||
Test Procedure | Type | Test Current | Initial State | Tripping or Non-tripping Time Limit | Expected Result | Remark |
A | B.C.D | 1.13In | Cold | t≤1h | no tripping | |
B |
B.C.D |
1.45In |
After test A |
t≤1h |
tripping |
The current steadily rises to the specified
value within 5s |
C | B.C.D | 2.55In | Cold | 1s<t<60s | tripping | |
D |
B | 3In |
Cold |
t≤0.1s |
no tripping |
Turn on the auxiliary switch to close the
current |
C | 5In | |||||
D | 10In | |||||
E |
B | 5In |
Cold |
t≤0.1s |
tripping |
Turn on the auxiliary switch to close the
current |
C | 10In | |||||
D | 20In |