Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Single-column Disconnector |
Still deciding? Get samples of US$ 80/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
A Load break switch is similar in structure to a disconnector (both have visible disconnection points in the disconnection state), but it can be used to open and close circuits, which in turn resembles a circuit breaker.
However, a circuit breaker can control any circuit, while aLoad break switch can only switch on or off load current, or switch off over load current, so it is only used to switch off and on circuits under normal conditions, not short circuit fault current. However, it is required that its structure can pass the fault current of short circuit time without damage.
Because the arc extinguishing device and contact of the Load break switch are designed to cut off and connect the load current, the Load break switch should be used with the fuse in most cases, and the latter is responsible for cutting off the short-circuit fault current.
The opening and closing frequency and operating life of load disconnecting switches are usually higher than those of circuit breakers.
Product Benefits
Easy to install
Safe reliable operation
Designed for harsh environments
Technical Data
Rated current Ie | 160A | 250A | 315A | 315H | 400A | 630A | 800A | ||||
Frame size | EHD-315 | EHD-630 | |||||||||
Thermal current (Ith) | 160 | 250 | 315 | 400 | 400 | 630 | 800 | ||||
Rated insulation voltage (Ui) | 1500 | 1500 | 1500 | 1500 | 1500 | 1500 | 1500 | ||||
Rated impulse withstand voltage Uimp (KV) | 12 | 12 | 12 | 12 | 12 | 12 | 12 | ||||
Code | Number of poles | Rated voltage | Utilisation category | Ie(A) | Ie(A) | Ie(A) | Ie(A) | Ie(A) | Ie(A) | Ie(A) | |
EHDN | 2P(1P+,1P-) | 4P(2P+,2P-) | 1000VDC | DC-PV1/DC-21B | 160 | 250 | 315 | 400 | 400 | 630 | 800 |
EHDT | 2P(1P+,1P-) | 4P(2P+,2P-) | 1500VDC | DC-PV1/DC-21B | 100 | 160 | 250 | 315 | 400 | 630 | 800 |
EHDT | 3P(2P+,1P-) | 6P(4P+,2P-) | 1500VDC | DC-PV1/DC-21B | - | - | 315 | 400 | - | - | - |
Number of poles | Rated voltage | Utilisation category | Ie(A) | Ie(A) | Ie(A) | Ie(A) | Ie(A) | Ie(A) | Ie(A) | ||
EHDN | 2P(1P+,1P-) | 4P(2P+,2P-) | 1000VDC | DC-PV2 | 160 | 250 | 315 | - | 400 | 630 | - |
EHDT | 2P(1P+,1P-) | 4P(2P+,2P-) | 1500VDC | DC-PV2 | 100 | 160 | 250 | - | 400 | 630 | - |
EHDT | 3P(2P+,1P-) | 6P(4P+,2P-) | 1500VDC | DC-PV2 | - | - | 315 | - | - | - | - |
The short-circuit capacity is between 1000 and 1500VDC (no protection) | |||||||||||
Rated short time withstand current lcw 1s (kAeff) Icw | 5 | 5 | 5 | 5 | 8 | 8 | 8 | ||||
Rated short-circuit making capacity lcm(kA peak)- 60 ms Icm | 10 | 10 | 10 | 10 | 10 | 10 | 10 | ||||
Cable | |||||||||||
Recommended Cu rigid cable cross section(mm) | 70 | 120 | 185 | 185 | 240 | 2×185 | 2×240 | ||||
Recommended Cu busbar width(mm) | 20 | 20 | 20 | 20 | 25 | 25 | 25 | ||||
Mechanical characteristics | |||||||||||
Durability (number of operating cycles) | 8000 | 8000 | 8000 | 8000 | 8000 | 8000 | 8000 | ||||
Number of cycles of operation with current | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 |