Customization: | Available |
---|---|
Type: | Signal Type Arrester |
Structure: | Protective Gap |
Still deciding? Get samples of US$ 18.6/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make at Made-in-china.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Class I + II (T1+T2) low voltage SPDs
Protection against transient overvoltagess for 230/400 V~ power networks (50/60 Hz).
SPDs compliant with EN/IEC 61643-11 standards
Recommended for main distribution boards
Class I+II (T1+T2) : SPDs tested and specified according to both T1 and T2 test classes
Product Benefits
Technical Data
Product model | |||||
IEC Electrical | |||||
Nominal AC Voltage (50/60Hz) | Uo /Un | 230V | |||
Maximum Continuous Operating Voltage (AC) | Uc | 275V | 320V | 385V | 440V |
Nominal Discharge Current (8/20 μs) | In | 25kA | 25kA | 25kA | 25kA |
Maximum Discharge Current (8/20 μs) | Imax | 100kA | 100kA | 100kA | 100kA |
Impulse Discharge Current (10/350 μs) | I Imp | 25kA | |||
Voltage Protection Level | Up | <1500V | <1500V | <1800V | <2000V |
Response Time | tA | <25ns | |||
Back-Up Fuse (max) | 315A gL | ||||
Short-Circuit Current Rating (AC) | I SCCR | 25kA / 50kA | |||
TOV Withstand 5s | UT | 335V | |||
UT | 440V | ||||
TOV 120min | Mode | Safe Fail | |||
Number of Ports | 1 | ||||
UL Electrical | |||||
Maximum Continuous Operating Voltage (AC) | MCOV | 275V | 320V | 385V | 440V |
Voltage Protection Rating | VPR | 900V | 1000V | 1200V | 1200V |
Nominal Discharge Current (8/20 μs) | In | 20kA | 20kA | 20kA | 20kA |
Short-Circuit Current Rating (AC) | I SCCR | 150kA | 150kA | 150kA | 200kA |
Mechanical & Environmental | |||||
Operating Temperature Range | Ta | -40oF to +158oF [-40oC to +70oC] | |||
Permissible Operating Humidity | RH | 5%…95% | |||
Atmospheric pressure and altitude | 80k Pa … 106k Pa / -500m … 2000m | ||||
Terminal Screw Torque | Mmax | 39.9 Ibf·in [2.0~2.5 N.m] | |||
Conductor Cross Section (max) | 2 AWG (Solid, Stranded) / 4 AWG (Flexible) | ||||
35mm2 (Solid, Stranded) / 25mm2 (Flexible) | |||||
Mounting | 35mm DIN Rail, EN 60715 | ||||
Degree of Protection | IP20(built-in) | ||||
Housing Material | Thermoplastic: Extinguishing Degree UL 94 V-0 | ||||
Thermal Protection | Yes | ||||
Operating State / Fault Indication | Green: ok / Red: failure | ||||
Remote Contacts (RC) | Optional | ||||
RC Switching Capacity | AC:250V / 0.5A; DC:250V / 0.1A; 125V / 0.2A; 75V / 0.5A | ||||
RC Conductor Cross Section (max) | 16AWG (Solid) / 1.5mm2 (Solid) |