IEC Electrical |
|
Nominal AC Voltage (50/60Hz) |
Uo /Un |
230V 230V 230V 400V |
Maximum Continuous Operating Voltage (AC) |
Uc |
275V 320V 385V 440V |
Nominal Discharge Current (8/20 μs) |
In |
20kA 20kA 20kA 20kA |
Maximum Discharge Current (8/20 μs) |
Imax |
50kA 50kA 50kA 50kA |
Impulse Discharge Current (10/350 μs) |
I Imp |
12.5kA 12.5kA 10kA 10kA |
Specific Energy |
W/R |
39kJ/Ω 39kJ/Ω 25kJ/Ω 25kJ/Ω |
Charge |
Q |
6.25As 6.25As 5As 5As |
Voltage Protection Level |
Up |
1500V 1500V 1800V 2000V |
Response Time |
tA |
<25ns |
Back-Up Fuse (max) |
160A gL |
Short-Circuit Current Rating (AC) |
I SCCR |
25kA / 50kA |
TOV Withstand 5s |
UT |
335V 335V 335V 580V |
|
UT |
440V 440V 440V 765V |
TOV 120min |
Mode |
Safe Fail Safe Fail Safe Fail Safe Fail |
Number of Ports |
1 |
UL Electrical |
Maximum Continuous Operating Voltage (AC) |
MCOV |
275V 320V 385V 440V |
Voltage Protection Rating |
VPR |
900V 1200V 1350V 1500V |
Nominal Discharge Current (8/20 μs) |
In |
20kA 20kA 20kA 20kA |
Short-Circuit Current Rating (AC) |
SCCR |
150kA 150kA 150kA 200kA |
Mechanical & Environmental |
Operating Temperature Range |
Ta |
-40oF to +158oF [-40oC to +70oC] |
Permissible Operating Humidity |
RH |
5%…95% |
Atmospheric pressure and altitude |
80k Pa … 106k Pa / -500m … 2000m |
Terminal Screw Torque |
Mmax |
39.9 Ibf·in [2.0~2.5 N.m] |
Conductor Cross Section (max) |
2 AWG (Solid, Stranded) / 4 AWG (Flexible) |
|
35mm2 (Solid, Stranded) / 25mm2 (Flexible) |
Mounting |
35mm DIN Rail, EN 60715 |
Degree of Protection |
IP20(built-in) |
Housing Material |
Thermoplastic: Extinguishing Degree UL 94 V-0 |
Thermal Protection |
Yes |
Operating State / Fault Indication |
Green: ok / Red: defect |
Remote Contacts (RC) |
Optional |
RC Switching Capacity |
AC:250V / 0.5A; DC:250V / 0.1A; 125V / 0.2A; 75V / 0.5A |
RC Conductor Cross Section (max) |
16AWG (Solid) / 1.5mm2 (Solid) |