EAP Series Surge Protection Device was designed and manufactured, complying standard GB/T18802.1 IEC/EN 61643-11 , Rated voltage 275V~,320V~,385V~,440V~,Maximum discharge current 100kA,High Energy Varistor, high effective for lightning protection.
Product Benefits
Technical Data
Product model | |||||
IEC Electrical | |||||
Nominal AC Voltage (50/60Hz) | Uo /Un | 230V | |||
Maximum Continuous Operating Voltage (AC) | Uc | 275V | 320V | 385V | 440V |
Nominal Discharge Current (8/20 μs) | In | 25kA | 25kA | 25kA | 25kA |
Maximum Discharge Current (8/20 μs) | Imax | 100kA | 100kA | 100kA | 100kA |
Impulse Discharge Current (10/350 μs) | I Imp | 25kA | |||
Voltage Protection Level | Up | <1500V | <1500V | <1800V | <2000V |
Response Time | tA | <25ns | |||
Back-Up Fuse (max) | 315A gL | ||||
Short-Circuit Current Rating (AC) | I SCCR | 25kA / 50kA | |||
TOV Withstand 5s | UT | 335V | |||
UT | 440V | ||||
TOV 120min | Mode | Safe Fail | |||
Number of Ports | 1 | ||||
UL Electrical | |||||
Maximum Continuous Operating Voltage (AC) | MCOV | 275V | 320V | 385V | 440V |
Voltage Protection Rating | VPR | 900V | 1000V | 1200V | 1200V |
Nominal Discharge Current (8/20 μs) | In | 20kA | 20kA | 20kA | 20kA |
Short-Circuit Current Rating (AC) | I SCCR | 150kA | 150kA | 150kA | 200kA |
Mechanical & Environmental | |||||
Operating Temperature Range | Ta | -40oF to +158oF [-40oC to +70oC] | |||
Permissible Operating Humidity | RH | 5%…95% | |||
Atmospheric pressure and altitude | 80k Pa … 106k Pa / -500m … 2000m | ||||
Terminal Screw Torque | Mmax | 39.9 Ibf·in [2.0~2.5 N.m] | |||
Conductor Cross Section (max) | 2 AWG (Solid, Stranded) / 4 AWG (Flexible) | ||||
35mm2 (Solid, Stranded) / 25mm2 (Flexible) | |||||
Mounting | 35mm DIN Rail, EN 60715 | ||||
Degree of Protection | IP20(built-in) | ||||
Housing Material | Thermoplastic: Extinguishing Degree UL 94 V-0 | ||||
Thermal Protection | Yes | ||||
Operating State / Fault Indication | Green: ok / Red: failure | ||||
Remote Contacts (RC) | Optional | ||||
RC Switching Capacity | AC:250V / 0.5A; DC:250V / 0.1A; 125V / 0.2A; 75V / 0.5A | ||||
RC Conductor Cross Section (max) | 16AWG (Solid) / 1.5mm2 (Solid) |