AC Isolator switches are devices or systems that isolate a particular circuit for maintenance and prevent currents from passing through. The main isolator switch, also known as an isolator, typically consists of two sets (or one set) of electrical contacts mounted in series. The line side is connected to a power supply outside the building.
AC Isolator Switch ensure an electrical circuit is completely de-energised for routine service and maintenance and can be shut down quickly in the event of an emergency. The switch separates the circuit from the main power source and discharges any current trapped in the circuit, rendering it safe to work on and ensuring fast shut down and the absence of any electrical current when an emergency stop is required.
Switch-disconnectors
EAS80- PM 80 R -3 RY -IM2
1 2 3 4 5 6 7
Code | Description | Code |
1 | Type of Switch disconnectors | EAS80- |
2 | Installation Form | DB:Rail mounting DC:Door interlocked PM:Panel mounting EL:Plastic enclosure box |
3 | Rated current(A) | 16:16A 20:20A 25:25A 32:32A 40:40A 63:63A 80:80A 80H:100A 100:100A 125:125A |
4 | Knob Lock | Nil:Without lock R:With lock |
5 | Poles | 2 2P 3 3P 4 4P 6 6P 8 8P (6P 8P For interlock mechanism) |
6 | Knob color | Nil:Blue knob BW:Black/white rotating handle G:Gray knob Optional with lock RY:Rotating red/yellow handle BB:Rotating black/black handle With lock without lock |
7 | Inter lock mechanism | IM2:sync IM31:normal close IM32:normal open |
Side Mount Add-on Poles
EAS80- PS R 16
1 2 3 4
No | Description | Code |
1 | Type of Switch disconnectors | EAS80- |
2 | Add on pole code | PS Sync disconnected PD Early-making PN N terminal PE Protecting earthing |
3 | Mounting type | Nil R DB/DC/EL front installation PM, reverse installation form |
4 | Rated current(A) | 16:16A 20:20A 25:25A 32:32A 40:40A 63:63A 80:80A 80H:100A 100:100A 125:125A |
Add-on auxiliary contacts
EAS80- P1 R
1 2 3
No | Description | Code |
1 | Type of Switch disconnectors | EAS80- |
2 | Auxiliary contacts Code | P1 1NO + 1NC P2 2NO |
3 | Mounting type | Nil R DB/DC/EL, front installation form PM reverse installation form |
Technical Data
Current(≤40°C) Agreed heating current | 16A | 20A | 25A | 32A | 40A | 63A | 80A | 100A | 100A | 125A | |||||||||||||||||||||||||||||||||||||||||||||||||||
IEC rated operational current Ie AC-21A/B(≤690V) |
16A/16A | 20A/20A | 25A/25A | 32A/32A | 40A/40A | 63A/63A | 80A/80A | 100A/100A | 100A/100A | 125A/125A | |||||||||||||||||||||||||||||||||||||||||||||||||||
IEC rated operational current Ie AC-22A/B |
415V | 16A/16A | 20A/20A | 25A/25A | 32A/32A | 40A/40A | 63A/63A | 80A/80A | 100A/100A | 100A/100A | 125A/125A | ||||||||||||||||||||||||||||||||||||||||||||||||||
500V | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
690V | 32A/40A | 40A/63A | 63A/80A | 63A/80A | 80A/100A | 100A/125A | |||||||||||||||||||||||||||||||||||||||||||||||||||||||
IEC rated operational current Ie AC-23A/B |
415V | 16A/16A | 20A/20A | 25A/25A | 32A/32A | 40A/40A | 63A/63A | 80A/80A | 100A/100A | 100A/100A | 125A/125A | ||||||||||||||||||||||||||||||||||||||||||||||||||
500V | 25A/25A | 63A/63A | 80A/80A | 100A/100A | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||
690V | 40A/40A | 63/63A | 63A/63A | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
IEC rated operational current Ie DC-21B |
110VDC | 16A | 20A | 25A | 32A | 40A | 63A | 80A | 100A | 100A | 125A | ||||||||||||||||||||||||||||||||||||||||||||||||||
250VDC | 16A | 20A | 25A | 32A | 40A | 63A | 80A | 100A | 100A | 125A | |||||||||||||||||||||||||||||||||||||||||||||||||||
400VDC | 16A |
20A | 25A | 25A | 40A | 63A | |||||||||||||||||||||||||||||||||||||||||||||||||||||||
IEC rated operational power (3 phase) AC-23A/B |
415V | 7.5KW | 9KW | 11KW | 15KW | 18.5KW | 30KW | 37KW | 45KW | 55KW | |||||||||||||||||||||||||||||||||||||||||||||||||||
500V | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
690V | 11KW | 15KW | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Short circuit withstand current of fuse protection (kA rms expected value) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Fuse class | 415V | 16A | 20A | 25A | 32A | 40A | 63A | 80A | 100A | 125A | |||||||||||||||||||||||||||||||||||||||||||||||||||
Rated conditional short-circuit current | 415V | 10kA | 15kA | 20kA | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Short circuit withstand current of circuit breaker for protection, any circuit breaker that can trip within 0.3s | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Rated short-time withstand current | 0.3S | 2.5kA | 3kA | 5kA | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Short circuit performance (unprotected) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Rated short-time withstand current | 1S | 1.0kA | 1.5kA | 2.5kA | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Rated short circuit making capacity | 0.8kA | 1.4kA | 2.1kA | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Cable cross section | 1.5~10mm² | 2.5~35mm² | 10~70mm² | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Rated insulation voltage Ui | 800V | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Rated impulse withstand voltage Uimp | 8kV | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Mechanical Endurance | 100000 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Ambient Temperature | Operating -25~+55°C Storage -40~+70°C |
Current(≤40°C) Agreed heating current |
63A | 80A | 100A | 63A | 80A | 100A | 63A | 80A | 100A | ||||||||||||||||||||||||||||||||||||||||||||||||||||
IEC rated operational current Ie AC-21A/B(≤690V) |
63A/63A | 80A/80A | 100A/100A | 63A/63A | 80A/80A | 100A/100A | 63A/63A | 80A/80A | 100A/100A | ||||||||||||||||||||||||||||||||||||||||||||||||||||
IEC rated operational current Ie AC-22A/B |
415V | 63A/63A | 80A/80A | 100A/100A | 63A/63A | 80A/80A | 100A/100A | 63A/63A | 80A/80A | 100A/100A | |||||||||||||||||||||||||||||||||||||||||||||||||||
500V | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
690V | 40A/63A | 63A/80A | 63A/80A | 40A/63A | 63A/80A | 63A/80A | 40A/63A | 63A/80A | 63A/80A | ||||||||||||||||||||||||||||||||||||||||||||||||||||
IEC rated operational current Ie AC-21A/B |
415V | 63A/63A | 80A/80A | 100A/100A | 63A/63A | 80A/80A | 100A/100A | 63A/63A | 80A/80A | 100A/100A | |||||||||||||||||||||||||||||||||||||||||||||||||||
500V | 63A/63A | 63A/63A | 63A/63A | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
690V | 40A/40A | 40A/40A | 40A/40A | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
IEC rated operational current Ie DC-21B | 110VDC | 63A | 80A | 100A | 63A | 80A | 100A | 63A | 80A | 100A | |||||||||||||||||||||||||||||||||||||||||||||||||||
250VDC | 63A | 80A | 100A | 63A | 80A | 100A | 63A | 80A | 100A | ||||||||||||||||||||||||||||||||||||||||||||||||||||
400VDC | 40A | 40A | 40A | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
IEC rated operational power (3 phase) AC-23A/B | 415V | 30KW | 37KW | 45KW | 30KW | 37KW | 45KW | 30KW | 37KW | 45KW | |||||||||||||||||||||||||||||||||||||||||||||||||||
500V | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
690V | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Short circuit withstand current of fuse protection (kA rms expected value) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Fuse class | 415V | 63A | 80A | 100A | 63A | 80A | 100A | 63A | 80A | 100A | |||||||||||||||||||||||||||||||||||||||||||||||||||
Rated conditional short-circuit current | 415V | 15kA | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Short circuit withstand current of circuit breaker for protection, any circuit breaker that can trip within 0.3s | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Rated short-time withstand current | 0.3S | 3kA | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Short circuit performance (unprotected) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Rated short-time withstand current | 1S | 1.5kA | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Rated short circuit making capacity | 1.4kA | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Cable cross section | 2.5~35mm² | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Rated insulation voltage Ui | 800V | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Rated impulse withstand voltage Uimp | 8kV | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Mechanical Endurance | 100000 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Ambient Temperature | Operating -25~+55°C Storage -40~+70°C |