Product Benefits :
Product Benefits :
When two poles are placed adjacent to each other, these channels form a tunnel resulting in effective air circulation around individual poles
Choice to use Busbar and/or cable in the same terminal,provides reliable termination
Product Benefits :
Product Benefits :
Product Benefits :
Product Benefits :
The AC Residual Current Circuit breaker is a safety appliance that protects personal safety and prevents electrical fires, can prevent electrical equipment from being damaged. It can be widely used in power distribution systems.
Residual current-operated circuit breakers (RCBO)with overcurrent protection are mainly suitable for applications that require both overcurrent protection (overload and short circuit)and ground-fault current protection. It can detect faults and trip in time to ensure the safety of staff and equipment. Can be applied to energy management systems, power supply, and distribution network automation, residential power monitoring, and complete sets of equipment.
Technical Data
Electrical Features | |
Mode | Electronic |
Type | A / AC |
Tripping curve | B C D |
Pole No. | 2P |
Rated voltage | 240V~ |
Rated frequency | 50/60Hz |
Overload Current Protection Characteristics | ||||||
Test Procedure | Type | Test Current | Initial State | Tripping or Non-tripping Time Limit | Expected Result | Remark |
A | B.C.D | 1.13In | Cold | t≤1h | no tripping | |
B |
B.C.D |
1.45In |
After test A |
t≤1h |
tripping |
The current steadily rises to the specified
value within 5s |
C | B.C.D | 2.55In | Cold | 1s<t<60s | tripping | |
D |
B | 3In |
Cold |
t≤0.1s |
no tripping |
Turn on the auxiliary switch to close the
current |
C | 5In | |||||
D | 10In | |||||
E |
B | 5In |
Cold |
t≤0.1s |
tripping |
Turn on the auxiliary switch to close the
current |
C | 10In | |||||
D | 20In |