An AC circuit breaker serves as a vital safety component in electrical systems, safeguarding circuits against the detrimental effects of excessive current caused by overloads or short circuits. Commonly deployed in residential, commercial, and industrial settings, these breakers ensure the continued security and operational integrity of electrical installations.
Safety
AC Circuit breakers help prevent electrical fires and damage to electrical equipment by interrupting the flow of current in case of a fault.
Convenience
AC Circuit breakers can be easily reset after resolving the issue that caused the trip, unlike fuses that need to be replaced.
Selectivity
AC Circuit breakers can be designed to trip at different current levels, allowing for better coordination and isolation of faulty circuits in a system.
Reliability
AC Modern circuit breakers are designed to operate with high accuracy and minimal maintenance, ensuring the long-term protection of electrical systems.
Product Benefits
Product Benefits
Product Benefits
Electrical Features | |
Rated current (In) | 1-63A |
Poles | 1P 2P 3P 4P |
Rated voltage (Ue) | 1P: 240/415V~ 2/3/4P:415~ |
Insulation voltage (Ui) | 500V |
Rated frequency | 50/60Hz |
Overload Current Protection Characteristics | ||||||
Test Procedure | Type | Test Current | Initial State | Tripping or Non-tripping Time Limit | Expected Result | Remark |
A | B.C.D | 1.13In | Cold | t≤1h | no tripping | |
B |
B.C.D |
1.45In |
After test A |
t≤1h |
tripping |
The current steadily
rise to the specified value within 5s |
C | B.C.D | 2.55In | Cold | 1s<t<60s(In≤32A) 1s<t<120s(In>32A) | tripping | |
D |
B | 3In |
Cold |
t≤0.1s |
no tripping |
Turn on the auxiliary
switch to close the current |
C | 5In | |||||
D | 10In | |||||
E |
B | 5In |
Cold |
t≤0.1s |
tripping |
Turn on the auxiliary
switch to close the current |
C | 10In | |||||
D | 20In |